The first voltage tester with current measurement is here: the testo 755-1. You can test electrical circuits or systems for voltage or de-energization, measure flow of current or current consumption and carry out continuity tests using a single instrument. In the process, the testo 755-1 voltage tester detects and selects all the electrical parameters automatically: you can just start measuring – without any switching on or selection.
The measuring tips, which can be quickly and simply exchanged, are also particularly user-friendly. This means you do not need to replace the whole instrument straight away in the event of damage. Just as practical: the integrated torch for illuminating dark measuring points.
The testo 755-1 current/voltage tester is a genuine all-rounder which will make your day-to-day work easier.
testo 755-1 current/voltage tester, including batteries, measuring tips, measuring tip caps, calibration protocol and instruction manual.
| General Technical Data | |
| Operating humidity | 0 to 75 %RH |
| Weight | 320 g |
| Dimensions | 199 x 62 x 40 mm |
| Operating temperature | -10 to +50 °C |
| Product colour | Black |
| Protection class | 4 IP64 |
| Standards | EN 61243-3; EN 61243-3; EN 61010-1 |
| Battery type | 2 AAA micro batteries |
| Display type | LCD (Liquid Crystal Display) |
| Display size | one-line |
| Storage temperature | -15 to +60 °C |
| Overvoltage Category | CAT IV 600V; CAT III 1000V |
| Authorizations | CSA; CE |
| Instrument Measurement Functions Measuring point illumination | yes |
| Display ligthing | yes |
| Hold | yes |
| Display (counts) | 4,000 |
| Autom. measurement parameter detection | yes |
| Measuring point illumination | yes |
| DC voltage | |
| Measuring range | 6 to 600 V |
| Resolution | max. 0.1 V |
| Accuracy | ± (1.5 % of mv + 3 Digit) |
| AC voltage | |
| Measuring range | 6 to 600 V |
| Resolution | max. 0.1 V |
| AC current | |
| Measuring range | 0.1 to 200 A |
| Resolution | max. 0.1 A |
| Accuracy | ± (3 % of mv + 3 Digit) |
| Resistance Resolution | |
| Measuring range | 30 to 100 kOhm |
| Accuracy | ± (1.0 % of mv + 5 Digit) |